[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023318":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},1023318,751,1,"单选题","送电线路与电信线路相对位置示意图如图15-2（电信线路系长途中继线、Ecd=1030V）,请按电信线路两端绝缘计算对地电压。 单相接地短路故障点在O点，C点对地电压为（）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","714V；",false,{"key":16,"text":17,"correct":14},"B","780V；",{"key":19,"text":20,"correct":14},"C","1530V；",{"key":22,"text":23,"correct":24},"D","772.5V。",true,"根据《输电线路对电信线路危险和干扰影响防护设计规程》（DI\u002FT5033-2006）的5.2.13条的有关规定及1款1》公式（5.2.13-1）。 已知：单相接地短路故障点在0点，电信线两端绝缘，Ecd=1O3OV,Lcd=15km,Lac=5km、Ldb=30km。 Uc=Ecd\u002F2（Lcd+2Ldb）\u002F（Lcd+Lac+Ldb） =1030\u002F2（15+2X30）\u002F50=772.5（V）",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]