[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023190":3},{"question":4,"library":22},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":17,"analysis":21},1023190,751,1,"单选题","某220kV线路，某段路径穿越工矿污秽区，据地网局审定的“污区分布图”，被划分为II级污移区，现拟选用XWP-70耐污型悬式绝缘子（高146cm泄漏距离400mm）请核算：",[11,14,16,19],{"key":12,"text":12,"correct":13},"A",false,{"key":15,"text":15,"correct":13},"B",{"key":17,"text":17,"correct":18},"C",true,{"key":20,"text":20,"correct":13},"D","根据《110~500kV架空送电线路设计技术规程》（DL\u002FT5092-1999）。 根据13页,9.0.4条,污秽区耐张绝缘子的片数,可不再比悬垂绝缘子串增加，故仍为15片。",{"id":6,"name":23,"category":24,"favorite":25},"电气工程师发输变电专业","建筑工程",0]