[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1023189":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1023189,751,1,"单选题","某220kV线路，某段路径穿越工矿污秽区，据地网局审定的“污区分布图”，被划分为II级污移区，现拟选用XWP-70耐污型悬式绝缘子（高146cm泄漏距离400mm）请核算： 悬垂绝缘子串需要的片数（）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","13；",false,{"key":16,"text":17,"correct":14},"B","14；",{"key":19,"text":20,"correct":21},"C","15；",true,{"key":23,"text":24,"correct":14},"D","16。","根据《110~500kV架空送电线路设计技术规程》（DL\u002FT5092-1999）。 42页，附录B，II级污秽区要求絲髙运行电压下爬电比距离为2.0~2.5cm\u002FkV。 n=（2~2.5）X220X1.1\u002F40=12.1~15.125（片） 由于耐污绝缘子高与标准绝缘子相同，故不得小于按过电压要求的最小值13片，为安全计,取15片。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]