[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022979":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1022979,751,1,"单选题","某火电厂装设2台600MW机组，高压厂用电每台机组设2段6kV工作母线，并设2段6kV公用母线。 主厂房汽机380V\u002F220V低压供电拟分成二段（A段及B段），计算负荷A段为893kVA,B段为1037kVA,重复负荷为601kV A，汽机低压工作变压器台数和容量为（）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","选择1台1600kVA变压器供2段母线；",false,{"key":16,"text":17,"correct":14},"B","选择3台1250kVA变压器供2段母线；",{"key":19,"text":20,"correct":21},"C","选择2台1600kVA变压器分别供2段母线，互为备用；",true,{"key":23,"text":24,"correct":14},"D","选择1台1250kVA及1台1600kVA变压器分别供电2段母线。","两段总负荷为893+1073—601=1329 (kVA),根据《火力发电厂厂用电设计技术规定》（DL\u002FT5153—2002)第4.7.5条。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]