[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022974":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1022974,751,1,"单选题","某火电厂装设2X300MW汽轮发电机组，发电机电压18kV,以发电机变压器组接至220kV母线，220kV母线采用双母线双分段接线，电厂最终为4X300MW容量。电厂每台机组设2段6kV髙压母线，由1台40\u002F25—25MV A、18±2X2.3 6.3kV分裂变压器向二段6kV母线供电。试选择备用\u002F启动变压器。 高压启动\u002F备用变压器采用分裂变压器、若电源引接点电压波动超过±5%,启动\u002F备用变压器的变比应采用（）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","242±2X2.5%\u002F6.3~6.3kV；",false,{"key":16,"text":17,"correct":14},"B","242±2X5%\u002F6.3~6.3kV；",{"key":19,"text":20,"correct":21},"C","242±8X1.25%\u002F6.3~6.3kV；",true,{"key":23,"text":24,"correct":14},"D","242±4X2.5\u002F6.3~6.3kV。","根据DL\u002FT 5153—2002第5.3.3条和附录H之H2,启动\u002F备用变压器的变比应采用242±8X1.25%\u002F6.3~6.3kV,",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]