[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022971":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},1022971,751,1,"单选题","某电厂装设2X300MW汽轮发电机组，每台机组厂用高压6kV母线设2段母线，发电机电压为18kV，厂用工作变压器由发电机出口引接。 考虑高压厂用变压器高压侧为无穷大电源，且6kV工作母线最大电动机反馈电流为12.5kA,为使髙压厂用电系统采用轻型电器设备，若髙压厂用变压器采用40\u002F25—25MVA分裂变压器时，其中穿越阻抗电压U'dl-2最小可选（）。(精确到小数点后2位）",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","16.5%；",false,{"key":16,"text":17,"correct":14},"B","17%；",{"key":19,"text":20,"correct":14},"C","14.5%；",{"key":22,"text":23,"correct":24},"D","15%。",true,"根据DL\u002FT 5153—2002附录M之M1，三相短路电流计算如下：轻型电器设备开断电流为40kA Ib=I-Id=40-12.5=27.5=Ij\u002F(Xx+Xt)=9.16\u002F0+Xt=9.16\u002FXt(无穷大电源Xx=0) X1=9.16\u002F27.5=0.3331=0.9Ud%XSj\u002F(100XSt)=0.9Ud%X100\u002F(100X40)=0.0225Ud% Ud%=0.3331\u002F0.0225=14.8。 故穿越阻抗电压最小可选择15%。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]