[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022967":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},1022967,751,1,"单选题","某火电厂装有4台300MW机组，发电机电压为20kV,每台发电机以发电机变压器组接入500kV系统，500kV采用3\u002F2断路器接线，出线2回。 若每2台机组设1台启动\u002F备用变压器，全厂设2段公用段，由1、2号机组高压厂用变压器供电，下述有错的是（）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","每台启动\u002F备用变压器高压侧设一台断路器；",false,{"key":16,"text":17,"correct":14},"B","两台启动\u002F备用变压器高压侧可共用一台断路器；",{"key":19,"text":20,"correct":14},"C","两台启动\u002F备用变压器容量各与1、2号机组，3、4号机组高压厂用变压器容量相同；",{"key":22,"text":23,"correct":24},"D","两台启动\u002F备用变压器采用相同的容量。",true,"根据《火力发电厂厂用电设计技术规定》(DL\u002FT5153—2002)第5.3.2.4.7.1、4.7.4条。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]