[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022966":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},1022966,751,1,"单选题","某火力发电厂装有2台600MW机组，发电机电压为22kV，以发电机变压器组接至500kV配电装置。高压厂用变压器从主变压器低压侧引接，请回答如下问题。 若高压厂用变压器高压侧三相短路电流为130k A，以分裂绕组额定容量为基准的半穿越阻抗电压为15%，6kV电动机反馈电流为13k A，6kV断路器开断电流可选择（）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","31.5kA；",false,{"key":16,"text":17,"correct":14},"B","40kA；",{"key":19,"text":20,"correct":14},"C","50kA；",{"key":22,"text":23,"correct":24},"D","A和B均可。",true,"根据DL\u002FT 5153—2002附录M之M1，三相短路电流计算如下，I=Ib+Id Id=13kA Ib=Ij\u002F(Xx+Xt) Xx=Sj\u002FSx=100\u002F(√3X130X22)=0.0202 Xt=O.9Ud%XSi\u002F(100XSt)=0.9X15X100\u002F(100X40)=0.3375X Xx+X1=O.3577 Ij=9.16kA IbkA Ib=9.16\u002F0.3577=25.61(kA) I=25.61+13=38.61(kA)故6kV断路器开断电流选择40kA。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]