[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022962":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},1022962,751,1,"单选题","水力发电厂低压厂用电系统，低压电器选择和组合原则如下，请进行判断。 厂用电系统发生短路时，应保证其供电回路各级保护电器有选择动作。在下述的低压电器组合中’正确的是（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","当支线采用断路器作短路保护时，干线可釆用断路器作保护，此时，干线上的断路器应带延时动作；",true,{"key":16,"text":17,"correct":18},"B","当支线采用熔断器作短路保护时，干线也采用熔断器作保护，千线上的熔断器熔件应比支线熔断器熔件大一级级差；",false,{"key":20,"text":21,"correct":18},"C","当支线采用断路器作短路保护时，干线可采用熔断器作保护，干线上的熔断器熔断时间在考虑误差后应取断路器的分闸时间的1.3倍；",{"key":23,"text":24,"correct":18},"D","当支线采用熔断器作短路保护时，干线可采用断路器作保护，此时，干线上的断路器应帝延时时间应取考虑误差后的熔断器熔断时间的1.2倍。","根据DL\u002FT 5164—2002第9.4.3条，正确的是A。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]