[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022961":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},1022961,751,1,"单选题","水力发电厂低压厂用电系统，低压电器选择和组合原则如下，请进行判断。 以下分断能力校验，有误的是（）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","校验主配电盘，重要分配电盘低压电器的分断能力时，应计及容量大于20kW的电动机反馈电流；",false,{"key":16,"text":17,"correct":14},"B","低压保护电器分断能力校检应采用安装地点的预期短路电流（周期分量有效值），其值应不大于断路器額定短路分断能力；",{"key":19,"text":20,"correct":14},"C","315kVA及以下的变压器校验短路分断能力时可不计及低压电动机反馈电流；",{"key":22,"text":23,"correct":24},"D","短路分断能力的校验应采用三相短路电流，三相四线制系统宜采用单相接地短路电流。",true,"根据《水力发电厂厂用电设计规程》（DL\u002FT 5164-2002)第2.6条，有误的是D。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]