[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022960":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1022960,751,1,"单选题","某火力发电厂厂用电电压采用6kV、380V\u002F220V,高压厂用电采用金属封闭铠装手车式开关柜，低压厂用电采用抽屉式开关柜，在开关柜的布置中，回答下列问题。 低压配电盘为单列布置，其盘后操作通道的最小宽赛应为（）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","0.8m；",false,{"key":16,"text":17,"correct":14},"B","1.0ms；",{"key":19,"text":20,"correct":21},"C","1.2m；",true,{"key":23,"text":24,"correct":14},"D","1.4m。","查DL\u002FT5153-2002表8.1.8,单列布置的低压配电盘盘后搡作通道的最小宽度应为1.2m。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]