[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022958":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},1022958,751,1,"单选题","某火力发电厂厂用电电压采用6kV、380V\u002F220V,高压厂用电采用金属封闭铠装手车式开关柜，低压厂用电采用抽屉式开关柜，在开关柜的布置中，回答下列问题。 髙压电动机及低压厂用变压器全部采用断路器对其供电，其中1号机组共有43块髙压开关柜，双列布置，假设开关柜尺寸为1800mmX1000mm，则配电室长度宜（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","不小于23m；",true,{"key":16,"text":17,"correct":18},"B","不小于24m；",false,{"key":20,"text":21,"correct":18},"C","不小于25m；",{"key":23,"text":24,"correct":18},"D","等于25m。","C 根据《火力发电厂厂用电设计技术规定》（DL\u002FT5153—2002)第8.1.4条，每段设1块备用柜，则最长一列柜长为23m,査表8.1.10，侧面维护通道1m，故配电室长度宜为23+2X1=25m。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]