[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022946":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},1022946,751,1,"单选题","关于火电厂高压厂用变压器容量和阻抗选择，下述各项叙述了选择的原则，请对其正确性进行判断。 容量为2MW及以下的高压电动机可不校验正常启动时的电压水平，电动机功率(kW)与变压器额定容量（kV A)比率为（）时也可不校验正常启动时的高压厂用电电压水平。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","小于20%；",false,{"key":16,"text":17,"correct":18},"B","不大于20%；",true,{"key":20,"text":21,"correct":14},"C","小于30%；",{"key":23,"text":24,"correct":14},"D","不大于30%.","根据DL\u002FT5153—2002第5.6.1、5.3.2、5.4.2条。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]