[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022936":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1022936,751,1,"单选题","高压厂用电系统采用高电阻接地，在中性点设备选择中，有如下问题值得研究。 若设专用的三相接地变压器，构成人为的中性点时，变压器采用Ynd接线，二次侧为开口三角形。变压器一次绕组绝缘需按线电压设计，其原因是（）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","系统单相接地时，绕组短时承受的过电压约为2. 6倍额定电压，故需使变压器绝缘有一定裕度；",false,{"key":16,"text":17,"correct":14},"B","根据经验；",{"key":19,"text":20,"correct":21},"C","单相接地时，变压器绕组将长时间承受系统的线电压；",true,{"key":23,"text":24,"correct":14},"D","单相接地时，中性点偏移为相电压，考虑非金属接地，绕组承受的电压大于相电压。","变压器一次绕组绝缘需按线电压设计，其原因是单项接地时，变压器绕组将长时间承受系统的线电压。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]