[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022932":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},1022932,751,1,"单选题","某500kV变电所装有两台主变压器，所用电设计确定了如下主要原则和内容，请判断其正确性。 所用电接线主要原则如下，下述各项有误的是（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","所用电变压器采用双绕组变压器，设置两台，分别从主变最低电压侧引接，主变压器采用有载调压，所用变压器采用无载谪压变庄器；",false,{"key":16,"text":17,"correct":18},"B","所用电采用380V\u002F220V中性点直接接地系统，采用单母线分段接线，两台所用变压器分接于两段母线上；",true,{"key":20,"text":21,"correct":14},"C","设置一台专用所用备用变压器，电源从35kV系统引接，采用有载调压变压器；",{"key":23,"text":24,"correct":14},"D","根接远动要求，变电所设置一套UPS装置。","根据《220kV~500kV变电所所用电设计技术规程》（DL\u002FT 5155—2002)第4.2.2条,接线为单母线，不是单母线分段。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]