[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022929":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1022929,751,1,"单选题","某装机2X300MW的火力发电厂，低压厂用电系统为中性点直接接地。每台机组设一台800kW的柴油发电机作交流保安电源。请对如下设计原则作出判断。 交流保安电源接线如下，其叙述不对的是（）。 A.柴油发电机电压和中性点接地方式与低压厂用电系统一致；",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","交流保安电源母线采用单母线接线；",false,{"key":16,"text":17,"correct":14},"B","低压厂用电系统变压器为1600kV",{"key":19,"text":20,"correct":21},"C","明备用方式接线，单母线接线，变压器接于对应母线，两段母线各引一回电缆与保安电源连接；",true,{"key":23,"text":24,"correct":14},"D","考虑机组脱硫保安负荷由机組保安电源供电。","根据 DL\u002FT5153—2002第4.6.1条，",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]