[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022925":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},1022925,751,1,"单选题","装机容量2X300MW火力发电厂设计中，需进行厂用电系统短路电流、电压调整、电动机启动时的电压校验等计算，其中： 高压厂用电短路电流计算采用的公式：XT= (0.9XUdXSj)\u002F(100XSe B)中的系数0.9是考虑（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","变压器担抗的负误差；",true,{"key":16,"text":17,"correct":18},"B","根据运行经验取的系数；",false,{"key":20,"text":21,"correct":18},"C","变压器阻抗的分教性；",{"key":23,"text":24,"correct":18},"D","A+C。","公式：XT=(0.9XUd%XSj)\u002F(100XS e.B)中的系数O.9是变压器阻抗的负误差，见《火力发电厂厂用电设计技术规定》(DL\u002FT5153—2002)附录M说明。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]