[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022920":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1022920,751,1,"单选题","某火力发电厂装有2X25MW机组，设有发电机母线，以35kV电压与3km外的220kV变电站35kV母线连接。电网供电，现扩建装设2X600MW机组，以500kV接入系统，若扩建机组厂用电率（未统计脱硫系统负荷）估算为5.8%。毎台机组设一台引接于发电机出口的厂用分裂工作变压器（不含脱硫系统负荷），两台机组设一台启动\u002F备用分裂变压器。 髙压厂用电厂用6kV电压，设置两段母线，经估算母线段最大单相电容电流为6.5A,直接接于髙压厂用变压器中性点的接地电阻为500Ω，对其单相接地保护以下说法不对的是（）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","厂用母线和厂用电源面路单相接地保护可利用通过接地电扭的零序电流实现；",false,{"key":16,"text":17,"correct":14},"B","厂用毋线和厂用电源回路单相接地保护可利用母线TV二次侧开口三角形的零序电压实现；",{"key":19,"text":20,"correct":21},"C","接地电流满足接地故障检测装里灵敏性要求，电动机回路应装设该装置，装置只能由反映零序方向的元件构成；",true,{"key":23,"text":24,"correct":14},"D","其他馈线回路接地保护只发信号。","根据DL\u002FT5153—2002第4.5.5、9.2.2条。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]