[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022919":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1022919,751,1,"单选题","某火力发电厂装有2X25MW机组，设有发电机母线，以35kV电压与3km外的220kV变电站35kV母线连接。电网供电，现扩建装设2X600MW机组，以500kV接入系统，若扩建机组厂用电率（未统计脱硫系统负荷）估算为5.8%。毎台机组设一台引接于发电机出口的厂用分裂工作变压器（不含脱硫系统负荷），两台机组设一台启动\u002F备用分裂变压器。 经技术经济比较该工程确定外引专用220kV线路作启动\u002F备用电源，启动\u002F备用变压器的中性点应（）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","经隔离开关接地；",false,{"key":16,"text":17,"correct":14},"B","隔离开关、避雷器及保护间隙并联接地；",{"key":19,"text":20,"correct":21},"C","直接接地；",true,{"key":23,"text":24,"correct":14},"D","B或C均可。","根据DL\u002FT5153—2002第4.5.5、9.2.2条。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]