[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022909":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},1022909,751,1,"单选题","某新建2X300MW火力发电厂为单元接线。厂用电系统采用6kV和380V两级电压，其中每台机组设 A、B两段6kV工作段，全厂设01 A、01B两段6kV公用段。 经估算，6kV高压厂用电工作B段所连设备的电缆总电容单相值为2.13μF,该厂用电系统宜采用（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","髙电阻接地；",false,{"key":16,"text":17,"correct":18},"B","低电阻接地；",true,{"key":20,"text":21,"correct":14},"C","消弧线圈接地（欠补偿）；",{"key":23,"text":24,"correct":14},"D","消弧线围接地（过补偿）。","根据《电力工程电气设计手册》（1)第3章第4节第一条，系统总电容按电缆电容的1.25倍考虑，单相接地电容电流Ic=1.73X6X314X1.25X2.13\u002F1000=8.7(A)。根据《火力发电厂厂用电设计技术规定》（DL\u002FT5153—2002)第4.2.1条。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]