[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022906":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},1022906,751,1,"单选题","某电厂装有2台600MW机组，每台机组设有2段6kV厂用高压母线，向各厂用电负荷供电，6kV采用手车式开关柜。6kV厂用母线接有1台6300kW给水泵电动机。 6kV厂用母线短路冲击电流为117k A，断路器动稳定保证值应选择（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","130kA；",true,{"key":16,"text":17,"correct":18},"B","110kA；",false,{"key":20,"text":21,"correct":18},"C","160kA；",{"key":23,"text":24,"correct":18},"D","180kA。","断路器动稳定保证值应大于厂用母线短路冲击电流，选择130kA。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]