[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022903":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},1022903,751,1,"单选题","某500kV变电所装设2组750MVA主变压器（由3台单相三绕组自耦变压器组成）各侧电压为525\u002F√3kV\u002F230\u002F√3±3X2.5%kV\u002F35kV,35kV侧接无功补偿装置，每台主变压器35kV无功补偿母线接1台厂用工作变压器，采用630kVA变压器，所用工作变压器35kV接入点电压波动达到辆定电压的±5%。 变压器的电压调整方式，范围和级电压为（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","35±2X2.5%\u002F0.4kV无励磁调压变压器；",true,{"key":16,"text":17,"correct":18},"B","35±3X2.5%\u002F0.4kV有载调压变压器；",false,{"key":20,"text":21,"correct":18},"C","35±8X1.25%\u002F0.4kV有载调压变压器；",{"key":23,"text":24,"correct":18},"D","35±2X5%\u002F0.4kV无励磁调压变压器。","根据DL\u002FT 5155-2002附录C之C2，变压器为35±3X2.5%kV\u002F0.4kV有载调压变压器。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]