[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022887":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},1022887,751,1,"单选题","计算某水电厂低压厂用电系统短路电流。 厂用电主母线三相短路，由厂用电变压器供给的短路电流周期分量为（）。(每相回路总电阻和总电抗分别为2.98MΩ和14.96MΩ）",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","14.02kA；",false,{"key":16,"text":17,"correct":14},"B","14.38kA；",{"key":19,"text":20,"correct":14},"C","14.82kA；",{"key":22,"text":23,"correct":24},"D","15.14kA。",true,"根据DL\u002FT5164—2002附录E之E2,厂用电变压器供给的短路电流周期分量为",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]