[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022878":3},{"question":4,"library":23},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":22},1022878,751,1,"单选题","计算某水电厂髙压厂用电系统短路电流（短路点为厂用电变压器二次侧出口）。已知：①电厂采用发电机一变压器单元接线，厂用电变压器接于机端、容量2000kVA,阻抗值为5%，二次侧电压10.5kV；②同时运行的高压电动机总容量小于1500kW。 短路点短路冲击电流ich为（）。 A.5.9kA；",[11,15,18],{"key":12,"text":13,"correct":14},"A","5.7kA；",false,{"key":16,"text":17,"correct":14},"B","5.5kA；",{"key":19,"text":20,"correct":21},"C","5.3k",true,"根据 DL\u002FT5164—2002附录E之E1，短路冲击电流ich=√2X1.78X2.2=5.54(kA)。",{"id":6,"name":24,"category":25,"favorite":26},"电气工程师发输变电专业","建筑工程",0]