[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022876":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},1022876,751,1,"单选题","计算某水电厂髙压厂用电系统短路电流（短路点为厂用电变压器二次侧出口）。已知：①电厂采用发电机一变压器单元接线，厂用电变压器接于机端、容量2000kVA,阻抗值为5%，二次侧电压10.5kV；②同时运行的高压电动机总容量小于1500kW。 高压厂用电系统短路电流计算原则，不妥的是（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","计算断路器开断时的直流分量和短路冲击电流；",true,{"key":16,"text":17,"correct":18},"B","同时运行的髙压电动机总容量不大于1500kW时，可不计电动机的反馈电流；",false,{"key":20,"text":21,"correct":18},"C","由机端或升高电压侧引接的电源，系统阻抗可忽略；",{"key":23,"text":24,"correct":18},"D","由地区电网引接的电源要计系统阻抗。","根据 DL\u002FT5164—2002第8.1.2条。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]