[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022869":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1022869,751,1,"单选题","某工程单元控制室采用控制和动力直流系统分设的方式，动力采用关端电池220V直流系统，蓄电池浮充电压为2.25V,该工程直流负荷统计如下： (1) O~1min放电电流为767.6A； (2) 1~60min放电电流为431.5A； (3) 60~90min放电电流为417.2A； (4) 90~180min放电电流为174.2A； (5) 180~480min放电电流为116.1A。 请根据上述参数回答下列问题。 蓄电池组0~1min的容量换算系数为0.867，请问第一阶段蓄电池组的计算容量为（）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","1500Ah；",false,{"key":16,"text":17,"correct":14},"B","1440Ah；",{"key":19,"text":20,"correct":21},"C","1240Ah；",true,{"key":23,"text":24,"correct":14},"D","1200Ah.","根据DL\u002FT5044—2004附录B.2.2的要求。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]