[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022857":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},1022857,751,1,"单选题","某工程110V控制负荷直流系统选用无端电池的500Ah铅酸蓄电池组，该工程事故初期(1min)放电电流为184.6A,蓄电池组在1.83V放电终止电压下放电1h的容量系数为0.656，蓄电池组至直流主屏的距离为50m，请根据上述数据回答下列问题。 蓄电池组至直流主屏电缆的计算截面面积为（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","548.6mm2；",true,{"key":16,"text":17,"correct":18},"B","308.8mm2；",false,{"key":20,"text":21,"correct":18},"C","274.3mm2；",{"key":23,"text":24,"correct":18},"D","154.4mm2。","直流电缆电阻计算公式：R=ρL\u002FS=0.0184X100\u002FS=1.84\u002FS，蓄电池组至直流主屏电缆所允许的最大电阻R=△U\u002FI=1.1\u002F328=1.84\u002FS,由此S=548.6.",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]