[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022855":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},1022855,751,1,"单选题","某工程110V控制负荷直流系统选用无端电池的500Ah铅酸蓄电池组，该工程事故初期(1min)放电电流为184.6A,蓄电池组在1.83V放电终止电压下放电1h的容量系数为0.656，蓄电池组至直流主屏的距离为50m，请根据上述数据回答下列问题。 蓄电池组至直流的允许压降为()。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","5.5V；",false,{"key":16,"text":17,"correct":14},"B","2.75V；",{"key":19,"text":20,"correct":14},"C","2.2V；",{"key":22,"text":23,"correct":24},"D","1.1V。",true,"根据DL\u002FT 5044—20047.3.2条的要求，允许压降为1%,即1.1V；",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]