[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022854":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},1022854,751,1,"单选题","某工程网络控制室110V直流系统，设计采用51只GFM2型阀控铅酸蓄电池，事故 放电末期电压确定为1.83V，在此电压下蓄电池组的容量系数为0. 555。直流系统负荷统计 如下：经常电流53.2A,事故放电初期（0~1min)电流184.6 A，事故持续放电(1~60min)电流184.6 A，断路器采用弹簧操动机构，无事故冲击放电。蓄电池组在1.83V终 止电压下，电流比例系数为2. 342。已知蓄电池组在0. 3C10。下放电1h的单体蓄电池电压为 2. 02V,在0. 4 C10下放电1h的单体蓄电池电压为1. 955V,在0. 5C10。下放电1h的单体蓄电 池电压为1. 90V。另外请根据上述已知条件回答下列问题。 最严重放电情况下，蓄电池组电压计算值为（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","103.02V；",false,{"key":16,"text":17,"correct":18},"B","99.71V；",true,{"key":20,"text":21,"correct":14},"C","96.9V；",{"key":23,"text":24,"correct":14},"D","93.5V。","根据DL\u002FT5044—2004附录C的相关公式。 各放电阶段单只电池的电压为1.955V。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]