[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022850":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},1022850,751,1,"单选题","某工程网络控制室110V直流系统，设计采用51只GFM2型阀控铅酸蓄电池，事故放电末期电压确定为1.83V,在此电压下蓄电池组的容量系数为0.555。直流系统负荷统计如下：经常电流53.2 A，事故放电初期（0~1min)电流184.6 A，事故持续放电（1~60min)电流184.6A,断路器采用弹簧操动机构，无事故冲击放电。蓄电池组在1.83V终止电压下，0~1min放电时的电流比例系数为2.342。1h放电时间电流比例系数为1，请根据上述已知条件回答下列问题。 采用电压控制计算法，蓄电池组容量的计算值为（）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","142Ah；",false,{"key":16,"text":17,"correct":14},"B","198.8Ah；",{"key":19,"text":20,"correct":14},"C","332.6Ah；",{"key":22,"text":23,"correct":24},"D","465.7Ah。",true,"根据DL\u002FT5044—2004附录B.2.1和附录B.2.2的要求计算，",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]