[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022810":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},1022810,751,1,"单选题","某工程单元控制室采用控制和动力直流系统分设的方式，动力采用无端电池220V直流系统’蓄电池举充电压为2.25V,,该工程直流负荷统计如下（实际容量为2400Ah)： (1) O~1min放电电流为767.6A； (2) 1~60min放电电流为431.5A； (3) 60~90min放电电流为417.2A； (4) 90~180min放电电流为174.2A； (5) 180~480min放电电流为116.1A。 请根据上述参数回答下列问题。 已知蓄电池组与直流屏之间的连接电缆电阻为1. 98mΩ，放电时间为0.02s时，蓄电池组内阻为10.30mn,放电时间为1.0s时，蓄电池组内阻为11.80m0,蓄电池组在直流屏端正负极短路时短路电流为（）。（蓄电池短路时单体电压为2.17V) A.0.02s短竑时19.11k A，1s短路时19.11kA； B.0.02s短路时18.11k",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","1s短路时16.03kA；",true,{"key":16,"text":17,"correct":18},"B","0.02s短路时17.11kA；",false,{"key":20,"text":21,"correct":18},"C","0.02s短路时16.11k",{"key":23,"text":24,"correct":18},"D","1s短路时14.03kA。","根据《电力工程直流系统设计技术规程》（DL\u002FT 5044—2004)附录G的相关公式。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]