[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022809":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},1022809,751,1,"单选题","某工程单元控制室采用控制和动力直流系统分设的方式，动力采用无端电池220V直流系统’蓄电池举充电压为2.25V,,该工程直流负荷统计如下（实际容量为2400Ah)： (1) O~1min放电电流为767.6A； (2) 1~60min放电电流为431.5A； (3) 60~90min放电电流为417.2A； (4) 90~180min放电电流为174.2A； (5) 180~480min放电电流为116.1A。 请根据上述参数回答下列问题。 蓄电池组1h终止放电电压为1.87V，容量换算系数0.41，蓄电池组与直流屏之间的距离为20m，负荷统计表中lmin实际放电电流为767.7 A，请问蓄电池组与直流屏之间的电缆截面面积计算值为（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","329.2mm2；",true,{"key":16,"text":17,"correct":18},"B","256.8mm2；",false,{"key":20,"text":21,"correct":18},"C","164.6mm2；",{"key":23,"text":24,"correct":18},"D","128.4mm2。","根据DL\u002FT 5044—2004附录D的相关公式。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]