[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022803":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},1022803,751,1,"单选题","某工程单元控制室采用控制和动力直流系统分设的方式，动力采用关端电池220V直流系统，蓄电池浮充电压为2.25V,该工程直流负荷统计如下： (1) O~1min放电电流为767.6A； (2) 1~60min放电电流为431.5A； (3) 60~90min放电电流为417.2A； (4) 90~180min放电电流为174.2A； (5) 180~480min放电电流为116.1A。 请根据上述参数回答下列问题。 蓄电池组90、120、179、180min的容量换算系数分别0.326、0.298、0.232、0.231，请问第四阶段蓄电池组的计算容量为（）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","4653Ah；",false,{"key":16,"text":17,"correct":14},"B","3139Ah；",{"key":19,"text":20,"correct":14},"C","2028Ah；",{"key":22,"text":23,"correct":24},"D","1512Ah。",true,"根据DL\u002FT5044—2004附录B.2.2的要求。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]