[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022759":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},1022759,751,1,"单选题","对发电机外部相间短路故障和作为发电机主保护的后备，当发电机容量为50MW及以上时，可装设负序过电流保护和单元件低压启动过电流保护. 对于单相过电流元件的整定，正确的说法是（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","动作电流按发电机额定负荷下可靠返回的条件整定，可靠系数取1.3~1.5，返回系数取0.85~0.95；",true,{"key":16,"text":17,"correct":18},"B","动作电流按发电机額定负荷下可靠返闻的条件整定，可靠系数取1.5~2.0，返闻系数取0.7~0.8；",false,{"key":20,"text":21,"correct":18},"C","C灵敏系数按主变压器高压侧母线金属性两相短路时流过保护的最小短路电流效验，灵敏系数要求大于2.0；",{"key":23,"text":24,"correct":18},"D","灵敏系数按主变压器高压侧母线金属性三相短路时流过保护的最小短路电流效验，灵敏系数要求大于2.0。","根据DL\u002FT684—19994.2.1条的要求选择。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]