[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022754":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1022754,751,1,"单选题","某工程600MW发电机差动保护TA变比为25000\u002F5 A，5P20,差动保护采用比率制动式，发电机定子线电压为22kV，额定电流15746 A，发电机端的最大外部短路电流为224k A，请根据上述已知条件回答下列问题。 差动保护的最小动作电流为（）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","3.15A；",false,{"key":16,"text":17,"correct":14},"B","1.56A；",{"key":19,"text":20,"correct":21},"C","0.63A；",true,{"key":23,"text":24,"correct":14},"D","0.16A,","根据DL\u002FT684—19994.1.1条的要求：",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]