[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022745":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},1022745,751,1,"单选题","某工程的主变压器容量为240MVA, XB=15%，高压侧为330kV，其最短线路的长度L=50km，X1=0.34Ω·m。 保护装于变压器高压侧时，阻抗保护整定值为（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","5.93Ω；",true,{"key":16,"text":17,"correct":18},"B","4.1Ω；",false,{"key":20,"text":21,"correct":18},"C","6.2Ω",{"key":23,"text":24,"correct":18},"D","4.5Ω。","见《电力工程电气设计手册》（2)算例29-6(第680页)。阻抗保护计算如下： 保护装于变压器高压侧时，安装处电流互感器变比nt=600\u002F1，电压互感器变比ny=330\u002F0.1。 保护整定值Zdt=KkKzZl=0.8X3X0.8X0.34X50=32.6(Ω) 归算到保护安装处的值Zdt= 当母线故障时Z1=0,因此灵敏度很髙。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]