[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022741":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},1022741,751,1,"单选题","240MV A、500\u002F220kV联络自耦变压器，差动保护动作电流为（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","70.5~75A；",false,{"key":16,"text":17,"correct":18},"B","78.4~90.5A；",true,{"key":20,"text":21,"correct":14},"C","95.3~105A；",{"key":23,"text":24,"correct":14},"D","105.5~110.8A。","解答过程： 根据DL\u002FT684-19995.1.3条的要求，变压器额定电流计算一般取中压侧额定电流，其值为 Ie=24000\u002F√3\u002F230=603(A) 保护差动继电器的动作电流Idz为 Idz=Kk?Klx?Ie=(0.13~0.15)Ie=(0.13~0.15)X603=78.4~90.5(A)",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]