[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022738":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},1022738,751,1,"单选题","200MW、15.75kV、cosφ=0.85发电机选用BCH—2型继电器作为主保护时（假设发电机外部三相短路时流经保护的最大短路电流Id.max=61200 A，机端两相金属性短路时I d.min=18.56A,TA变比为12000\u002F5)。 灵敏系数为（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","2；",false,{"key":16,"text":17,"correct":18},"B","3.71；",true,{"key":20,"text":21,"correct":14},"C","5.02；",{"key":23,"text":24,"correct":14},"D","4.5.","根据DL\u002FT684—19994.1条的要求： 以发电机孤立运行时，机端两相金属性短路校验",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]