[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022736":3},{"question":4,"library":23},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":21,"analysis":22},1022736,751,1,"单选题","200MW、15.75kV、cosφ=0.85发电机选用BCH—2型继电器作为主保护时（假设发电机外部三相短路时流经保护的最大短路电流Id.max=61200 A，机端两相金属性短路时I d.min=18.56A,TA变比为12000\u002F5)。 保护动作电流为（）。 A.3500A；",[11,15,18],{"key":12,"text":13,"correct":14},"A","5086A,",false,{"key":16,"text":17,"correct":14},"B","8060A；",{"key":19,"text":20,"correct":14},"C","11213","","根据DL\u002FT684—19994.1条的要求： 发电机额定电流为Ie=200000\u002F√3\u002F15.75\u002F0.85=8625(A) 1)按躲过外部短路时最大不平衡电流整定 2)按躲过电流互感器二次回路断线时的电流整定Idz=KkIe=1.3X8625=11213(A) 保护动作电流取1)、2)中最大值11213A。",{"id":6,"name":24,"category":25,"favorite":26},"电气工程师发输变电专业","建筑工程",0]