[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022721":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1022721,751,1,"单选题","某220kV变电所，220kV主接线为双母线（I母和II母）带专用旁路断路器接线，装设有母线保护和断路器失灵保护，对母线保护和断路器失灵保护的动作行为进行分析判断。 当220kV I母上的一条220kV线路发生单相接地故障，本侧220kV线路断路器拒动，以下断路器失灵保护的动作行为中，正确的是（）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","跳开母联断路器；",false,{"key":16,"text":17,"correct":14},"B","跳开I段母线上全部断路器；",{"key":19,"text":20,"correct":21},"C","以较短时限跳开母联，再经一时限跳开I段母线上全部断路器；",true,{"key":23,"text":24,"correct":14},"D","跳开母联断路器及II段母线上全部断路器。","根据GB 14285—20064.9.3.2节的相关规定.",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]