[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022709":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1022709,751,1,"单选题","—个220kV变电所，经稳定计算220kV出线发生三相短路，必须快速切除故障，否则不能满足系统稳定要求。 以下配置的主保护正确的是（）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","每回220kV线路各配置一套全线速动的徵机高頻保护作为主保护；",false,{"key":16,"text":17,"correct":14},"B","每回线各配里一套微机阶段式相间距离和接地矩离作为主保护；",{"key":19,"text":20,"correct":21},"C","每回线各配置两套全线速动的微机高频保护作为主保护；",true,{"key":23,"text":24,"correct":14},"D","每回线各配置两套?阶段式相间距离和接地距离作为主保护，","根据GB 14285—20064.6.2条和《电力系统微机继电保护技术导则》（DL\u002FT769-2001)3.2节的相关规定。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]