[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022703":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},1022703,751,1,"单选题","对变压器相间短路后备保护，请回答下列问题。 低电压启动的过电流保护的动作电流取值与过电流保护相同，其低电压元件的整定要求为（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","按躲过正常运行时可能出现的最低电压整定，一般最低运行电压取值为银定电压的0.9倍，可靠系数取1.1~1.2，返回系数取1.05~1.25；按躲过电动机自启动时的电压整定，当低电压继电器接在变压器低压例时，动作电压取值为頦定电压的0.5~0.6倍，接在变压器高压側时，动作电压取值为額定电压的0.7倍。",true,{"key":16,"text":17,"correct":18},"B","按躲过正常运行时可能出现的最低电压整定，一般’最低运行电压取伹为额定电压的0.9倍，可靠系数取1.1~1.2，返田系数取0.85~0.95；.按躲过电动机自启动时的电压整定，当低电压继电器接在变压器低压側时，动作电压取值为額定电压的0.7倍，接在变压器高压侧时，动作电压取值为额定电压的0.5~0.6倍，",false,{"key":20,"text":21,"correct":18},"C","按躲过正常运枰时可能出现的表低电压整定，一般最低运行电压取值为额定电压的0.9倍，可靠系数取1.1~1.2,返回系数取0.85~0.95；按躲过电动机自启动时的电压整定，当低电压继电器接在变压器低压側时，动作电压取植为额定电压的0.5~0.6倍，接在变压器.高压侧时，动作电压取值为頦定电压的0.7倍。",{"key":23,"text":24,"correct":18},"D","按躲过正常运行时可能出现的最低电压整定，一般最低运行电压取值为额定电压的0.9倍，可靠系数取1.1~1.2，返回系数取1.05~1.25；按躲过电动机自启动时的电压整定，当低电压继电器接在变压器低压側时，动作电压取值为额定电压的0.7倍，接在变压器高压側时，动作电压取值为额定电压的0.5~0.6倍。","根据DL\u002FT684-19995.5条的要求选择。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]