[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022696":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1022696,751,1,"单选题","某工程4台600MW发电机变压器组’主变压器髙压侧差动保护用TA变比为2000\u002F1 A，TPY。主变压器高压侧TV—次电压为500\u002F√3kV，二次星形电压为0.1\u002F√3kV和二次开口三角电压100V，主变压器容量为3X240MV A，主变压器变比为550\u002F√3-X2.5%\u002F22kV,Ud=14%,YNdll,主变压器低压侧差动保护TA变比为16000\u002F1A,TPY0主变压器高压侧三相短路时，短路点系统侧电流27.5kA’发电机侧短路电流为9.882A,主变压器低压侧三相短路时，系统侧短路电流为93.7kA,本台发电机短路电流为105.3k A，其他发电机短路电流为25.6kA。变压器差动保护采用比率制动型，请根据上述已知条件回答下列问题 比率制动型差动保护最小动作电流取差动回路额定电流的0.3倍，则实际计算值为()(以主变压器低压侧为基准，高压侧配置中间电流互感器)。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","0.126A;",false,{"key":16,"text":17,"correct":14},"B","0.216A;",{"key":19,"text":20,"correct":21},"C","0.354A；",true,{"key":23,"text":24,"correct":14},"D","0.615A。","根据DL\u002FT684—19995.1.3条的要求。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]