[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022695":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},1022695,751,1,"单选题","某工程4台600MW发电机变压器组’主变压器髙压侧差动保护用TA变比为2000\u002F1 A，TPY。主变压器高压侧TV—次电压为500\u002F√3kV，二次星形电压为0.1\u002F√3kV和二次开口三角电压100V，主变压器容量为3X240MV A，主变压器变比为 550\u002F√3-2X2.5%\u002F22kV,Ud=14%,YNdll,主变压器低压侧差动保护TA变比为16000\u002F1A,TPY0主变压器高压侧三相短路时，短路点系统侧电流27.5kA’发电机侧短路电流为9.882A,主变压器低压侧三相短路时，系统侧短路电流为93.7kA,本台发电机短路电流为105.3k A，其他发电机短路电流为25.6kA。变压器差动保护采用比率制动型，请根据上述已知条件回答下列问题 差动保护用T A，正确的接线形式是（）。 A.高压側TA 二次接线应为三角形，低压侧接线应为星形；高压侧差动回路二次額定电流0.72A,低压侧为1.18A；",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","高压侧TA二次接线应为星形，低压例接线应为三角形；高压侧差动回路二走額定电流0.72A,低压側为1.18A；",true,{"key":16,"text":17,"correct":18},"B","高压侧TA二次接线应为三角形，低压侧接线应为星形；高压侧差动回路二次額定电流0.42",false,{"key":20,"text":21,"correct":18},"C","低压侧为2.04A；",{"key":23,"text":24,"correct":18},"D","高压侧TA二次接线应为星形，低压例接线应为三角形；高压侧差动田路二次額定电流0.42A,低压側为2.04A。","根据DL\u002FT684—19995.1.3条的要求。",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]