[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022409":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},1022409,751,1,"单选题","发电厂的控制室采用灯光监视. 对于控制室灯光监视的控制信号回路，完整的说法是（）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","采用控制开关KK的位里与断路器的位里不对应接线，正常合闸时红灯亮，跳闸时绿灯亮，故障时红灯闪光；",false,{"key":16,"text":17,"correct":14},"B","采用控制开关控制，红、绿灯监视跌、合闸回路；",{"key":19,"text":20,"correct":14},"C","用控制开关控制，正常时指示灯不亮，故障时指示灯亮；",{"key":22,"text":23,"correct":24},"D","采用控制开关KK的位里与断路器位里不对应接线，用红、绿灯监视断路器跳、合闸回路，正常合闸时红灯亮，跳闸时绿灯亮，故障时绿灯闪光。",true,"依据 DL\u002FT5136—2001第7.1.2条.",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]