[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022375":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":12,"analysis":25},1022375,751,1,"单选题","在B类电气装置的接地装置的等电位连接接线时，以下不是标准要求的措施是（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","应采取防止杂散电流的绝缘措施；",true,{"key":16,"text":17,"correct":18},"B","等电位连接主母线的最小截面应不小于装置最大保护线截面的一半，并不应小于6mm2，当采用铜线时，其截面不宜大于25mm2;",false,{"key":20,"text":21,"correct":18},"C","连接两个外露导电部分的辅助等电位连接线，其截面不应小于接至该两个外露导电部分的较小保护线的截面；",{"key":23,"text":24,"correct":18},"D","当建筑物的水管被用作接地线或保护线时，水表必须跨接连接，其连接线的截面应根据其功能要求而采用适当的截面。","",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]