[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022371":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},1022371,751,1,"单选题","在发电厂中，对铁路轨道和管道防静电接地的接地位置、接地线、接地极布置方式等都提出了明确的要求.下面要求不正确的是（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","铁路机道、管道及金属桥台，应在其始端、末端、分支处以及每隔50m处设防静电接地；",false,{"key":16,"text":17,"correct":18},"B","厂区内的铁路应在两处用绝缘装置与外部轨道隔离，两处绝缘装置间的距离应小于一列火车的长度；",true,{"key":20,"text":21,"correct":14},"C","净距小于1OOmm的平行或交叉管道，应每隔20m用金属线跨接；",{"key":23,"text":24,"correct":14},"D","不能保持良好电气接触的阀门、法兰、弯头等管道连接处也应跨接，跨接线可采用直径不小于8mm的圆钢。","",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]