[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022360":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":16,"analysis":25},1022360,751,1,"单选题","现已知某变电站接地网的均压带为不等间距布置，地网导体等效直径d=0.03m;沿长宽方向布置的均压带根数n1=15，n2=6；接地网的长度和宽度L1=323.5m，L2=170m;水平均压带埋设深度h=0.8m;地网的网孔数m=（n1—1）（n2-1）=14X5=70。请计算各有关相关系数和最大跨步电位差系数。 最大接触电位差系数Ktmax的计算值是（）。",[11,15,19,22],{"key":12,"text":13,"correct":14},"A","0.086；",false,{"key":16,"text":17,"correct":18},"B","0.111;",true,{"key":20,"text":21,"correct":14},"C","0.165；",{"key":23,"text":24,"correct":14},"D","1.131。","根据DL\u002FT 621—1997P18附录B中的B2，c）2）,根据计算公式计算如下",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]