[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022358":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":22,"analysis":25},1022358,751,1,"单选题","某发电厂配电装置的接地装置，接地网的接地电阻计算值为0. 2020;计算用的入地短路电流采用值为9.122kA,最大接触电位差系数的计算值为0.22；最大跨步电位差系数的计算值为0.108.据此，请计算最大接触电位差和最大跨步电位差. 接地装置接地网外地表面的最大跨步电位差为（）。",[11,15,18,21],{"key":12,"text":13,"correct":14},"A","158V,",false,{"key":16,"text":17,"correct":14},"B","175V；",{"key":19,"text":20,"correct":14},"C","180V；",{"key":22,"text":23,"correct":24},"D","199V。",true,"根据DL\u002FT 621-1997P18附录B中的B2，根据计算公式计算如下Umax=KmaxUg=O.108X1843=199（V）",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]