[{"data":1,"prerenderedAt":-1},["ShallowReactive",2],{"q-1022357":3},{"question":4,"library":26},{"id":5,"libraryId":6,"type":7,"typeLabel":8,"stem":9,"options":10,"answer":19,"analysis":25},1022357,751,1,"单选题","某发电厂配电装置的接地装置，接地网的接地电阻计算值为0. 2020;计算用的入地短路电流采用值为9.122kA,最大接触电位差系数的计算值为0.22；最大跨步电位差系数的计算值为0.108.据此，请计算最大接触电位差和最大跨步电位差. 接地装置接地网地表面的最大接触电位差为（）。",[11,15,18,22],{"key":12,"text":13,"correct":14},"A","286V；",false,{"key":16,"text":17,"correct":14},"B","312V；",{"key":19,"text":20,"correct":21},"C","405V；",true,{"key":23,"text":24,"correct":14},"D","534V。","根据DL\u002FT 621-1997P18附录B中的B2，根据计算公式计算如下Umax=KmaxUg=O.22X1843=405（V）",{"id":6,"name":27,"category":28,"favorite":29},"电气工程师发输变电专业","建筑工程",0]